“Config errors” Area

Indicators are grey (not active function), green (everything’s OK), or red (error).In case of error some temporary files with “err” extension will be created on ram disc “/ram2”. Those files will be deleted on reboot.It’s possible to check ERR files on /ram2 (and view content) using the GF_Project integrated diagnostic tool “SID”.“Config errors” area icons have the following meaning:
  • C: CAN configuration error. Grey: CAN not used or not available Green: configuration OK Red: configuration error. Check file /ram2/Con_net.err
  • G: GDNet configuration error. Grey: GDNet not used or not available Green: configuration OK Red: configuration error. Check file /ram2/Gdnet_cfg.err
  • E: EtherCAT configuration error. Grey: EtherCAT not used or not available Green: configuration OK Red: configuration error. Check file /ram2/ ECATmgr_cfg.err
  • B: Local Bus ePCLogic400 configuration error Grey: Local Bus not used or not available Green: configuration OK Red: configuration error. Check file /ram2/Bus400_cfg.err
  • F: ICT configuration error. Grey: ICT not used or not available (e.g.: ModuBus/TCP) Green: configuration OK Red: configuration error. Check file /ram2/Ict_cfg.err
  • V: PLC variables configuration error. Grey: PLC 1131 not used or not available Green: configuration OK Red: configuration error. Check file /ram2/Map1131vars.err
  • D: Datalog configuration error Grey: Datalogs not defined Green: configuration OK Red: configuration error. Check the file /ram2/datalog.err.