Column “Over 1”
This alarm detect tasks execution time greater than a customizable set-point.The signals are OFF/grey (OK), or red (error detected)
- FAST: the 1131 code inside the “FAST” task has overtaken the maximum allowed time, specified on pre-defined variable GPV_ALARMTIME_WDOG1131.
- NORMAL: the 1131 code inside the “NORMAL” task has overtaken the maximum allowed time, specified on pre-defined variable GPV_ALARMTIME_WDOG1131_NORMAL.
- SLOW: the 1131 code inside the “SLOW” task has overtaken the maximum allowed time, specified on pre-defined variable GPV_ALARMTIME_WDOG1131_SLOW.